Wire Size Calculator
How it Works
01Voltage & Current
Enter system voltage (120/240/480) and load in amps. Pick AC 1-ph, 3-ph, or DC.
02One-Way Length
Distance from source to load in feet. Round-trip is doubled automatically.
03Material & Temp
Copper or aluminum. Insulation temp rating 60 / 75 / 90 °C.
04AWG + Voltage Drop
Recommended AWG, ampacity, actual voltage drop — both branch 3% and feeder 5% tested.
What is a Wire Size Calculator?
A wire size calculator is the universal conductor sizer every electrician, solar installer, and electrical estimator keeps one click away. Unlike preset amp calculators (100A, 200A, 12V), this tool handles the full range: AC or DC, any voltage, any amperage, any run length, copper or aluminum, using NEC Table 310.16 ampacity and the standard voltage-drop formula. It's the calculator that replaces three different reference cards in your toolbox.
The underlying math runs in two steps. First, find the minimum AWG for the load per NEC 310.16 at your selected insulation temperature column (60°C for old-house NM-B, 75°C for most modern terminations, 90°C for free-air derated applications). Second, apply the voltage-drop formula — V = (K × L × I) ÷ CM for AC one-way, or V = (2 × K × L × I) ÷ CM for DC round-trip — where K is the conductor resistivity constant (12.9 for copper, 21.2 for aluminum at 75°C), L is distance, I is current, and CM is circular mils. If drop exceeds the target (3% for branch circuits, 5% for combined feeder + branch), the calculator upsizes AWG until drop is within limits.
Inputs: amperage, voltage, one-way run length, conductor material (copper or aluminum), insulation temperature rating, and AC or DC system. Output includes required AWG, actual voltage drop %, ampacity margin, wattage lost to resistance, and whether the final size is ampacity-limited or drop-limited. Also reports typical breaker/fuse size for the circuit.
Typical use cases: branch circuit sizing (15A to 60A residential), feeder sizing (60A to 400A subpanels and services), solar home-run sizing (10 AWG to 4/0 for string PV), RV and marine DC (16 AWG to 4/0 for 12V-48V systems), and commercial 208V/480V three-phase (any AWG). For the specialized applications (100A residential service, 12V DC, 220V appliances), use the dedicated calculators in the same family.
"How the Wire Size Calculator Works
Wire Size Formula
Voltage Drop = (2 × K × L × I) ÷ Circular Mils
- K = 12.9 Ω·cmil/ft for copper at 75°C
- K = 21.2 Ω·cmil/ft for aluminum at 75°C
- L = one-way length in feet (factor of 2 accounts for return path)
- I = current in amps
Solving for minimum circular mils: cmils = (2 × K × L × I) ÷ max voltage drop
Then pick the smallest AWG whose circular mils ≥ calculated minimum AND whose ampacity ≥ load.
Example: 20 Amp Circuit, 100 ft Run, 120V
Load: 20A at 120V. Length: 100 ft. Copper. Max 3% drop = 3.6V.
- Min circular mils = (2 × 12.9 × 100 × 20) ÷ 3.6 = 14,333 cmils
- 10 AWG = 10,380 cmils → too small (voltage drop)
- 8 AWG = 16,510 cmils → OK
- 8 AWG ampacity (75°C) = 50A → massive headroom for 20A
- Actual drop = (2 × 12.9 × 100 × 20) ÷ 16,510 = 3.12V = 2.6%
Without voltage-drop, 12 AWG would have been enough for 20A (25A ampacity) — but the 100ft run pushes it to 8 AWG.
Who uses a wire size calculator?
AWG Reference Table — Copper at 75°C
| AWG | Ampacity | Circular Mils | Typical Use |
|---|---|---|---|
| 14 | 20A | 4,110 | 15A branch circuits |
| 12 | 25A | 6,530 | 20A branch circuits |
| 10 | 35A | 10,380 | 30A dryer / well pump |
| 8 | 50A | 16,510 | 40-50A range, EV charger |
| 6 | 65A | 26,240 | 60A AC, subpanel feeder |
| 4 | 85A | 41,740 | 70-85A feeder |
| 3 | 100A | 52,620 | 100A service feeder |
| 2 | 115A | 66,360 | 100-125A feeder w/ drop |
| 1 | 130A | 83,690 | 125A feeder |
| 1/0 | 150A | 105,600 | 150A service |
| 2/0 | 175A | 133,100 | 150A long run |
| 3/0 | 200A | 167,800 | 200A service |
| 4/0 | 230A | 211,600 | 200A long run |
Key Takeaways
A universal wire-size calculator is only as good as the two checks it runs: ampacity (can the wire safely carry the current without overheating?) and voltage drop (does the wire deliver the rated voltage at the load?). Skip either check and you end up with undersized cable that passes inspection but runs hot, or oversized cable that wastes hundreds of dollars in copper with no performance benefit.
Every new circuit or service must also respect the surrounding code: overcurrent protection matches the wire (not the load), conduit fill stays within NEC Chapter 9 Table 1 limits, ground conductors follow NEC 250.66 (service grounds) or 250.122 (equipment grounds), and all terminations are torqued to the manufacturer spec. This calculator handles the conductor math; a licensed electrician and a pulled permit handle the rest. For anything larger than a simple branch circuit, always involve the AHJ and pull the inspection ticket.
"Wire Size Calculator FAQs
What size wire do I need for a 20 amp circuit?
What size wire for 30 amps?
What size wire for 50 amps?
What size wire for 100 amp service?
What size wire for 200 amp service?
How do I calculate voltage drop?
What is the difference between copper and aluminum wire?
What is the NEC voltage drop recommendation?
Does wire length matter for wire size?
Can I use a smaller wire if I upgrade the breaker?
Disclaimer
Educational reference. For permit / inspection, always verify with a licensed electrician and local AHJ amendments.